Page 187 - publication

SEO Version

technical data
Introduction
Couplings
Outlets
Fittings
Val
ves &
Accesso
ries
High
Pressure
Advanced Copper
Method (IPS)
DI-LOK
®
Nipples
Plain-End
Fittings
HDPE
Couplings
Sock-It
®
Fittings
Stainless
Steel Method
Roll
Groovers
Installation
& Assembly
Special
Coatings
Design
Services
Technical
Data
Master Format
3 Part Specs.
Pictorial
Index
CTS Copper
System
www.anvilintl.com
187
G
R
U
V
L
O
K
WATER & AIR
Service
Gasket Grade
Air, (no oil vapors) Temp. -40°F to 230°F (-40°C to 110°C)
E
Air, (no oil vapors) Temp. -40°F to 350°F (-40°C to 177°C)
L
Air, Oil vapor Temp. -20°F to 150°F (-29°C to 66°C)
T
Air, Oil vapor Temp. 20°F to 300°F (-7°C to 149°C)
O
Water, Temp to 150°F (66°C)
E/T
Water, Temp to 230°F (110°C)
E
Water, Acid Mine
E/T
Water, Chlorine
(E/O)
Water, Deionized
E/T
Water, Seawater
E/T
Water, Waste
E/T
Water, Lime
E/T
STANDARD GASKETS
Grade Temp.
Range Compound Color
Code
General Service Applications
E
-40°F to
+230°F
(-40°C
to110°C)
EPDM Green
Water, dilute acids, alkalies, salts, and many chemical
services not involving hydrocarbons, oils, or gases.
Excellent oxidation resistance.
NOT FOR USE WITH HYDROCARBONS
T
-20°F to
+180°F
(-29°C to
82°C)
Nitrile
(Buna-N) Orange
Petroleum products, vegetable oils, mineral
oils, and air contaminated with petroleum oils.
NOT FOR USE IN HOT WATER SERVICES
GASKET GRADE INDEX & GASKET
RECOMMENDATION
GASKET GRADE INDEX
GASKET RECOMMENDATION LISTING
VACUUM SERVICE
Where more than one gasket grade is shown the preferred gasket grade is listed frst. Where the gas-
ket grade is shown in parentheses, Contact a Gruvlok Representative for an engineering evaluation
and recommendation. Specify gasket grade when ordering. Use Gruvlok lubricant on gasket. Check
gasket color code to be certain it is recommended for the service intended.
Unless otherwise noted, all gasket listings are based upon 100°F (38°C) maximum temperature
service conditions.
For services not listed, contact a Gruvlok Representative for recommendation.
*Contact a Gruvlok Representative for service evaluation.
LARGER SIZES:
Contact a
Gruvlok Representative for
more information.
SPECIAL GASKETS
Grade Temp.
Range Compound Color
Code
General Service Applications
O
+20°F to
+300°F
(-20°C to
149°C)
Fluoro
Elastomer Blue
High temperature resistance to oxidizing acids,
petroleum oils, hydraulic fuids, halogenated,
hydrocarbons and lubricants
L
-40°F to
+350°F
(-40°C to
177°C)
Silicone Red
Gasket
Dry, hot air and some high temperature chemical
services.
E
Type
A
-40°F to
+150°F
(-40°C to
66°C)
Pre-
Lubricated Violet
Wet & Dry (oil free air) Pipe in Fire Protection
Systems. For dry pipe systems, Gruvlok Xtreme
Temperature Lubricant is required
PETROLEUM PRODUCTS
Service
Gasket Grade
Crude Oil - Sour
T
Diesel Oil
T
Fuel Oil
T
Gasoline, Leaded
T
Gasoline, Unleaded*
(O)
Hydraulic Oil
T
JP-3, JP-4 and JP-5
T/O
JP-6, 100°F (38°C) Maximum Temp.
O
Kerosene
T
Lube Oil, to 150°F (66°C)
T
Motor Oil
T
Tar and Tar Oil
T
Transmission Fluid —Type A
O
Turbo Oil #15 Diester Lubricant
O
VACUUM SERVICE
Size
Vacuum Level
Gasket Recommendation
1" - 6" (25 - 150mm)
0" - 29.92" Hg
Standard or Flush Gap
8" - 12" (200 - 300mm)
0" - 15 Hg
Standard or Flush Gap
1
1
/
2
" - 12" (40 - 200mm)
0" - 29.92 Hg
Flush Gap
The lists are provided as an aid in selecting the optimum gasket grade for a
specifc application to assure the maximum service life.
The recommendations have been developed from current information
supplied by manufacturers of the elastomers, technical publications, and
industry applications. The information supplied should be considered as a
basis for evaluation but not as a guarantee.
Selection of the optimum gasket grade for a specifc service requires the
consideration of many factors; primarily temperature, fuid concentration,
and continuity of service. Unless otherwise noted, all gasket recommendations
are based on 100°F (38°C) maximum temperature service condition. Where
more than one gasket grade is shown, the preferred grade is listed frst.
Combinations of fuids should be referred to a
Gruvlok Representative for an engineering evaluation
and recommendation. In unusual or severe services,
gasket materials should be subjected to simulated service
conditions to determine the most suitable gasket grade.
Gasket recommendations apply only to Gruvlok gaskets. Contact a Gruvlok
Representative for recommendations for services not listed. These listings
do not apply to Gruvlok Butterfy Valves.
All Gruvlok products marked with UL/ULC Listed, FM approved VdS and/or LPC
symbols are Listed/Approved with EPDM material. For other Listed/Approved
materials, please contact a Gruvlok Representative for more information.
GL-2.10