Positioners & Controls
294
Dixon Sanitary 2014
800.789.1718
XPO Series Digital Positioner
Features and Benefits
microprocessor based valve positioner
user friendly, menu-driven programming with LCD display,
multi-lingual
local push button configuration - no hand held device of PC
necessary
low air consumption and dependable mechanical design
modular design - available with position feedback, micro
switches and fail free options
aluminum housing - NEMA 4X IP 65 enclosure standard
ATEX, FM, CSA, IEC and EX approvals available
Enclosure Options
NEMA 4X IP 65 standard
explosion proof
intrinsically safe / non-incendive
Communications
Hart
no communications
foundation fieldbus
profibus
Options
gauge block with gauges
micro switches
4-20
ma transmitter
filter regulator - coalescing
fail freeze
Specifications
rotation: 25-120 degrees
maximum air supply: 90 PSI
air delivery: 6.0 SCFM @ 90 PSI
ambient temperature: -40°F to 185°F
stroke: .4 to 4" (longer stokes - POA)
connections: ¼" NPT air, ½" NPT cable
air consumption: .015 SCFM
characteristic curves: linear, equal %, 1:25, 1:50, 25:1, 50:1
or user configurable with 20 reference points
characteristic deviation: = 0.5%
deadband 0.1%, adjustable to 10%
resolution (A/D conversion): 4000 steps, Hart: 16,000 steps,
FF and PA
vibration influence: = 1% up to 10 G and 80 Hz
sample rate: 20 msec
air supply: must be free of oil, water and dust to DIN / ISO
8573-1
pollution and oil contents according to Class 3 dew
point 20 K below operating temperature
Dimensions
3.62
6.63
(4)
M6 TAP EQ.
SPACED ON 1.97 B.C.
3.52
45
°
(4)
M6 TAP EQ.
SPACED ON 1.97 B.C.
45
°
3.96
4.87
7.78
XPO-D series
XPO-X series
S