Page 152 - publication

SEO Version

gruvlok installation and assembly
www.anvilintl.com
152
FIG. 7011
Standard Coupling
2
Turn the gasket inside out and
slide the gasket completely
over one of the pipe ends. Turning
the gasket inside out will reduce
the stretching necessary to put
the gasket into position. Ideally,
approximately 75% of the pipe’s
gasket-sealing surface, (Dimension
A) should be visible when the
gasket is in proper position. This
will aid in step 4.
3
Lubricate the gasket sealing
lips. The use of Gruvlok
lubricants ensures compatibility
between the lubricant and the
gasket.
4
Pull the two pipes into contact
aligning the pipe ends.
CAUTION:
Be careful not to pinch fngers
during this step. Working your way around
the circumference of the pipe, fip the
gasket toward the pipe end so that the
proper side is facing out. The end of this
procedure will result in the gasket snapping
into place. Position the gasket centrally
between the grooves of the two pipe ends.
1
Inspect the pipe ends making
sure the criteria, in the
Gruvlok Large Diameter Pipe Roll
and Cut Groove Specifcations, are
met.
5
Lubricate the exterior surface
of the gasket. This helps pre-
vent pinching of the gasket during
assembly.
6
Secure the housings about the
pipes making sure the coupling
keys are engaged in the pipe end
grooves. Hint: For horizontal assem-
bly, place housing segment on top
of the pipe to support the weight
of the housing segment. Secure the
adjacent housing with an oval neck
track bolt and heavy hex nut and
then rotate the secured housings,
again balancing the weight of the
housings on the top of the pipe.
Continue this procedure for all
segments.
7
Firmly torque each bolt. The
specifed minimum torque for
each nut is 600 ft.-lbs. The speci-
fed maximum torque for each nut
is 800 ft.-lbs.
8
Installation of the Figure
7011 Standard Coupling is
completed.
CAUTION:
Use of an impact wrench is not recommended because the torque output can
vary signifcantly due to many variables including air pressure supply, battery strength and
operational variations.
CAUTION:
Proper torquing of coupling bolts is required to obtain specifed performance.
Over torquing the bolts may result in damage to the bolt and/or casting which could
result in pipe joint separation. Under torquing the bolts may result in lower pressure
retention capabilities, lower bend load capabilities, joint leakage and pipe joint separation.
Pipe joint separation may result in signifcant property damage and serious injury.
GL-2.10